What are the mapping models and concurrency architectures for translating IEC 60870-5-104 telecontrol to DLMS/COSEM?

Scheduled Pinned Locked Moved General Discussion
iec104telecontrolgatewaydlmsdistributionaut
4 Posts 3 Posters 35 Views 1 Watching
  • Oldest to Newest
  • Newest to Oldest
  • Most Votes
Reply
  • Reply as topic
Log in to reply
  • C Offline
    C Offline
    carlos_mendez
    wrote on last edited by
    #1

    🛡️ Technical Redaction & Safe Harbor Warning:
    Substation telemetry maps and dispatch IP configurations have been neutralized.

    In distribution automation (DTU/FTU edge gateways), SCADA master stations communicate over IEC 60870-5-104 (TCP Port 2404), while field revenue and feeder meters communicate via DLMS / COSEM (IEC 62056-53 Clause 6.2) reading voltage 1.0.32.7.0.255 and energy 1.0.1.8.0.255.
    Gateways must translate 104 information object addresses (IOA) to DLMS OBIS codes for telemetry, tele-signaling, and remote tele-control.
    How do engineers architect concurrent polling and event translation to prevent SCADA response timeouts during general interrogation?

    1 Reply Last reply
    0
    • M Offline
      M Offline
      marcus_vance
      wrote on last edited by
      #2

      The golden rule in 104-to-DLMS gateway design per Green Book Section 7.1 is: Never synchronously poll DLMS serial meters during a 104 General Interrogation (C_IC_NA_1).

      The recommended decoupled architecture:

      [ SCADA 104 Master ] <=== TCP 2404 ===> [ Gateway Real-time Memory Cache ]
                                                        ▲
                                              Background Polling & Push Daemon
                                                        ▼
      [ DLMS Meter Network ] <=== RS-485/TCP 4059 <=====┘
      
      1. Telemetry (YC / M_ME_NC_1 Float):
        Gateway maintains periodic background polling loops (e.g. 1s for Voltage/Current, 15s for Energy). Master interrogation answers immediately from RAM cache.
      2. Tele-signaling (YX / M_SP_NA_1 Event):
        DLMS Unsolicited Push (Class 40 0.0.25.9.0.255) alarms trigger spontaneous 104 ASDU transmissions (Cause of Transmission COT=3).
      3. Tele-control (YK / C_SC_NA_1 Breaker Control):
        Translates directly to DLMS Class 70 (Disconnect Control 0.0.96.3.10.255) Method 1/2.
      1 Reply Last reply
      0
      • A Offline
        A Offline
        alex_turner
        wrote on last edited by
        #3

        On the other hand, remote breaker operations (104 YK) require strict two-step execution (Select -> Execute):
        When receiving 104 Execute, the gateway holds the 104 context and dispatches a High-Level Security DLMS Class 70 ACTION with a 3000ms timeout per Blue Book Chapter 4.6.
        Only when the meter confirms execution with action-result: success does the gateway return 104 Command Confirmation (COT=7).

        1 Reply Last reply
        0
        • C Offline
          C Offline
          carlos_mendez
          wrote on last edited by
          #4

          Per IEC 60870-5-104 Clause 7.2 and IEC 62056-53 Clause 8.2, our gateway now translates the DLMS ACTION response:

          C7 01 C1 00 00
          

          into 104 ASDU confirmation within 120ms, eliminating SCADA command timeouts while preserving metrological security.

          1 Reply Last reply
          0

          Hello! It looks like you're interested in this conversation, but you don't have an account yet.

          Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.

          With your input, this post could be even better 💗

          Register Login
          Reply
          • Reply as topic
          Log in to reply
          • Oldest to Newest
          • Newest to Oldest
          • Most Votes


          • Login

          • Don't have an account? Register

          • Login or register to search.
          Powered by NodeBB Contributors
          • First post
            Last post
          0
          • Categories
          • Recent
          • Tags
          • Popular
          • World
          • Users
          • Groups