Why does Disconnect Control (Class 70) Method 2 return Success (0x00) while output_state remains false?
-
[!WARNING]
Technical Redaction & Safe Harbor Notice:
All communication captures, system titles, and cryptographic parameters in this thread have been sanitized and neutralized. Real utility meter identifiers, production encryption keys (GUEK/GAK/MK), SIM IMSIs, and proprietary network envelopes have been substituted with standard IEC 62056 synthetic test vectors. Do not post unredacted production captures or live cryptographic keys.We are troubleshooting an unexpected relay issue during field commissioning of 200 polyphase commercial smart meters over IEC 62056-47 TCP/IP (port 4059). After a remote load-shedding event, our HES sends a remote reconnection command via Class 70 (
Disconnect Control, OBIS0.0.96.3.10.255), invoking Method 2 (remote_reconnect).The meter returns an immediate
Action-Response-Normalindicating success (0x00
00 01 00 01 00 01 00 05 C7 01 C1 00 00However, when we immediately read back Attribute 2 (
output_state) to verify contact closure, the meter returns03 00(boolean: false
00 01 00 01 00 01 00 04 C4 01 C2 00 03 00The downstream load remains completely de-energized. We contacted the meter manufacturer's FAE, and the classic response was "It works fine on our lab bench tool." Meanwhile, the Wireshark DLMS dissector confirms our Action APDU is 100% syntactically valid. Why is the meter acknowledging reconnection with success (
0x00) while physically refusing to close the breaker? -
Carlos, before suspecting a faulty relay coil or broken firmware, look closely at the Disconnect Control state machine in DLMS UA Blue Book (17th Ed.) Section 4.5.3 and IEC 62056-62 Clause 4.5.3.
Your assumption that invoking Method 2 (
remote_reconnect) guarantees immediate physical contact closure is where the trap lies. In COSEM Class 70, breaker behavior is governed by Attribute 4 (control_mode) and Attribute 3 (control_state
control_mode = 1(Manual): Meter cannot be remotely reconnected.control_mode = 2(Remote only): Method 2 transitions the breaker directly fromDisconnected (0)toConnected (1), immediately closing the contact (output_state = true).control_mode = 3(Manual reconnect / Consumer safety): Method 2 only transitionscontrol_statefromDisconnected (0)toReady_for_reconnection (2)! Physical closure requires the end-user to press the physical push-button on the meter terminal.control_mode = 5 / 6: Timed reconnection modes with safety arming.
Because of European electrical safety regulations (preventing unattended energization of consumer premises), factory default meters are almost universally shipped with
control_mode = 3.When you send Method 2, returning
0x00(Success) means the state transition fromDisconnectedtoReady_for_reconnectionsucceeded. Have you read Attribute 3 and Attribute 4 to inspect the activecontrol_state? -
David, you nailed it. We just ran a readback on Attribute 3 (
control_state) and Attribute 4 (control_mode) on our bench unit:00 01 00 01 00 01 00 06 C4 01 C3 00 16 02 16 0316 02:control_state = 2(Ready_for_reconnection)16 03:control_mode = 3
As soon as we manually pressed the optical/display button on the meter front panel, the contactor gave a loud mechanical click, and
output_stateimmediately flipped to03 FF(true).This explains why this meter batch passed official DLMS CTT (Conformance Test Tool) certification with flying colorsโCTT only checks that the APDU returns
0x00, completely ignoring whether physical voltage was restored downstream! For our unmanned rooftop solar installations, we cannot have technicians pushing buttons. How do we safely reconfigurecontrol_modeto Mode 2 over the air? -
To enable direct remote reconnection without human button intervention, your HES must reconfigure Attribute 4 (
control_mode) to Mode2(Remote only) under the Management Association.Here is the verified
Set-Request-NormalAPDU writingcontrol_mode = 2(enum0x16 0x02
00 01 00 01 00 01 00 0F C1 01 C4 00 46 00 00 60 03 0A FF 04 00 16 02Meter response (
Set-Response-Normal, success):00 01 00 01 00 01 00 04 C5 01 C4 00Once
control_modeis set to2, invoking Method 2 immediately energizes the trip coil, movingcontrol_statedirectly toConnected (1)and settingoutput_statetotrue(0x03 0xFF).Here is the complete Gurux.DLMS Python snippet to handle this automated commissioning flow:
from gurux_dlms.objects import GXDLMSDisconnectControl from gurux_dlms.objects.enums import ControlMode, ControlState def force_remote_reconnect(client, obis_code="0.0.96.3.10.255"): relay = GXDLMSDisconnectControl(obis_code) # 1. Read current control mode client.read(relay, 4) # 2. Reconfigure to Mode 2 (Remote Only) if armed for manual button if relay.controlMode != ControlMode.MODE_2: relay.controlMode = ControlMode.MODE_2 client.write(relay, 4) # 3. Invoke Method 2 (remote_reconnect) client.method(relay, 2, 0, "integer8") # 4. Verify output state is confirmed true client.read(relay, 2) if not relay.outputState: raise RuntimeError("Physical breaker failed to close.") return TrueBy enforcing
control_mode = 2prior to reclosing, unmanned substations can be restored automatically without field truck rolls.
Hello! It looks like you're interested in this conversation, but you don't have an account yet.
Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.