IEC 62056-21 Mode E Optical Probe Sign-On and Baud Rate Switch Failure

Scheduled Pinned Locked Moved General Discussion
optical-probeiec-62056-21mode-ebaudrateserial
3 Posts 2 Posters 14 Views 1 Watching
  • Oldest to Newest
  • Newest to Oldest
  • Most Votes
Reply
  • Reply as topic
Log in to reply
  • C Offline
    C Offline
    carlos_mendez
    wrote on last edited by
    #1

    Field Troubleshooting Case

    When connecting an optical probe to legacy IEC/DLMS hybrid meters, the sign-on handshake succeeds at 300 bps (7E1 parity), but switching to high-speed HDLC mode at 9600 bps or 19200 bps fails, terminating the session.

    Optical Sign-on Trace (300 Baud, 7E1)

    1. Client -> Meter: /?!<CR><LF> (2F 3F 21 0D 0A)
    2. Meter -> Client: /LGZ4ZMD4104400.B34<CR><LF>
      • Identification character: Z (Baud rate identification)
      • Mode character: 2 (Mode E - transition to DLMS/HDLC)
    3. Client -> Meter: ACK/Option Select: <ACK> 2 5 2 <CR><LF> (06 32 35 32 0D 0A)
      • 2: Normal protocol mode
      • 5: Baud rate 9600 bps
      • 2: Mode E (HDLC)

    The Failure

    After sending the ACK message, the gateway switched the serial port baud rate to 9600 bps immediately without inserting the required delay $T_a$, causing the first HDLC SNRM frame to be sent while the meter optical receiver was still re-configuring its UART clock.

    1 Reply Last reply
    0
    • E Offline
      E Offline
      elena_rostova
      wrote on last edited by
      #2

      Also note that during Mode E sign-on, the parity changes: Initial handshake is 300 baud, 7 data bits, Even parity, 1 stop bit (7E1). Once the baud rate switch occurs for DLMS/HDLC, the UART MUST switch to 8 data bits, No parity, 1 stop bit (8N1).

      1 Reply Last reply
      0
      • E Offline
        E Offline
        elena_rostova
        wrote on last edited by
        #3

        Also note that during Mode E sign-on, the parity changes: Initial handshake is 300 baud, 7 data bits, Even parity, 1 stop bit (7E1). Once the baud rate switch occurs for DLMS/HDLC, the UART MUST switch to 8 data bits, No parity, 1 stop bit (8N1).

        1 Reply Last reply
        0

        Hello! It looks like you're interested in this conversation, but you don't have an account yet.

        Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.

        With your input, this post could be even better 💗

        Register Login
        Reply
        • Reply as topic
        Log in to reply
        • Oldest to Newest
        • Newest to Oldest
        • Most Votes


        • Login

        • Don't have an account? Register

        • Login or register to search.
        Powered by NodeBB Contributors
        • First post
          Last post
        0
        • Categories
        • Recent
        • Tags
        • Popular
        • World
        • Users
        • Groups