DLMS Single-Phase vs Three-Phase OBIS Register Mapping Reference
-
Quick Reference Table: Standard Electrical Measurement OBIS Codes
Measurement Total Phase A (L1) Phase B (L2) Phase C (L3) Class ID Active Power (+P) 1.0.1.7.0.2551.0.21.7.0.2551.0.41.7.0.2551.0.61.7.0.2553 (Register) Active Power (-P) 1.0.2.7.0.2551.0.22.7.0.2551.0.42.7.0.2551.0.62.7.0.2553 (Register) Reactive Power (+Q) 1.0.3.7.0.2551.0.23.7.0.2551.0.43.7.0.2551.0.63.7.0.2553 (Register) Voltage (RMS) N/A 1.0.32.7.0.2551.0.52.7.0.2551.0.72.7.0.2553 (Register) Current (RMS) N/A 1.0.31.7.0.2551.0.51.7.0.2551.0.71.7.0.2553 (Register) Power Factor 1.0.13.7.0.2551.0.33.7.0.2551.0.53.7.0.2551.0.73.7.0.2553 (Register) Frequency 1.0.14.7.0.255N/A N/A N/A 3 (Register) Active Energy (+A) 1.0.1.8.0.2551.0.21.8.0.2551.0.41.8.0.2551.0.61.8.0.2553 / 4 (Ext Reg) Active Energy (-A) 1.0.2.8.0.2551.0.22.8.0.2551.0.42.8.0.2551.0.62.8.0.2553 / 4 (Ext Reg) Bookmark this reference for field data validation!
-
Very handy reference! Especially useful when validating neutral current measurements, which use
1.0.91.7.0.255on four-wire meter installations.
Hello! It looks like you're interested in this conversation, but you don't have an account yet.
Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.