OBIS 1.0.32.7.0.255 Phase A Voltage Scaler-Unit 0xFF Parsing Bug (-1 vs 255 Exponent)

Scheduled Pinned Locked Moved General Discussion
obisscaler-unitregisterclass-3voltage
4 Posts 3 Posters 18 Views 1 Watching
  • Oldest to Newest
  • Newest to Oldest
  • Most Votes
Reply
  • Reply as topic
Log in to reply
  • S Offline
    S Offline
    sarah_jenkins
    wrote on last edited by
    #1

    Overview

    When querying Class 3 (Register) object 1.0.32.7.0.255 (Phase A Instantaneous Voltage), our data collector parsed a raw voltage value of 2200 with scaler 0xFF and produced a catastrophic measurement reading: 2200000000000000000000 V (2.2 x 10^27 V).

    DLMS APDU Response Trace

    C4 01 C1 00 00 02 02 12 08 98 02 02 0F FF 16 23
    

    ASN.1 Type Dissection

    • C4 01 C1: GET-Response-Normal (Invoke-Id-And-Priority C1)
    • 00 00: Data-Access-Result success (0)
    • 02 02: Structure of 2 elements
      • 12 08 98: Element 1 -> double-long-unsigned (Value = 2200 / 0x0898)
      • 02 02: Element 2 -> Structure of 2 elements (Scaler_Unit_Type)
        • 0F FF: Scaler -> Integer8 (0xFF)
        • 16 23: Unit -> enum (35 = 0x23 = Volts V)

    Root Cause

    Per DLMS Blue Book Section 4.3.3, the scaler field is of type Integer8 (signed 8-bit integer) in two's complement representation.

    • 0xFF = -1 (Scaling factor is $10^{-1} = 0.1$)
    • Correct calculation: $2200 \times 10^{-1} = 220.0\text{ V}$
    • The bug: The parsing library treated 0xFF as uint8_t (255), evaluating $2200 \times 10^{255}$ and overflowing database decimal columns!
    1 Reply Last reply
    0
    • E Offline
      E Offline
      elena_rostova
      wrote on last edited by
      #2

      This is one of the classic pitfalls in DLMS COSEM client implementations!

      Here is the safe deserialization snippet in Python:

      import struct
      
      def decode_scaler_unit(scaler_byte, unit_enum):
          # 'b' ensures signed 8-bit integer interpretation (-128 to 127)
          signed_scaler = struct.unpack('b', bytes([scaler_byte]))[0]
          multiplier = 10 ** signed_scaler
          return signed_scaler, multiplier
      
      scaler, mult = decode_scaler_unit(0xFF, 35)
      print(f"Scaler: {scaler}, Multiplier: {mult}, Voltage: {2200 * mult} V")
      # Output: Scaler: -1, Multiplier: 0.1, Voltage: 220.0 V
      
      1 Reply Last reply
      0
      • D Offline
        D Offline
        david_miller
        wrote on last edited by
        #3

        Note that for Class 4 (Extended Register) and Class 5 (Demand Register), the scaler-unit structure is identical, but is followed by a status octet-string or bit-string and an optional capture_time (Octet-String, 12 bytes). If you don't enforce signed int8 decoding across all register classes, power factor and reactive energy registers with negative scalers will corrupt downstream analytics.

        1 Reply Last reply
        0
        • S Offline
          S Offline
          sarah_jenkins
          wrote on last edited by
          #4

          Thanks Elena! We applied the signed int8 cast in the collection pipeline parser. All phase voltages (A/B/C: 1.0.32.7.0.255, 1.0.52.7.0.255, 1.0.72.7.0.255) now correctly read 220.4V, 219.8V, and 220.1V.

          1 Reply Last reply
          0

          Hello! It looks like you're interested in this conversation, but you don't have an account yet.

          Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.

          With your input, this post could be even better 💗

          Register Login
          Reply