What is the standard intuitive structure of OBIS 6-tuple codes (A.B.C.D.E.F) in Blue Book?

Scheduled Pinned Locked Moved General Discussion
beginnerobisbluebookcosemiec62056-62
3 Posts 3 Posters 18 Views 1 Watching
  • Oldest to Newest
  • Newest to Oldest
  • Most Votes
Reply
  • Reply as topic
Log in to reply
  • C Offline
    C Offline
    carlos_mendez
    wrote on last edited by
    #1

    🛡️ Technical Redaction & Safe Harbor Warning:
    Proprietary tariff schemes and meter registers have been replaced with standard IEC 62056-61 OBIS definitions.

    When reading the DLMS Blue Book Ed. 17 (IEC 62056-62 Clause 5.1), the 6-tuple OBIS hierarchy A.B.C.D.E.F (e.g. 1.0.1.8.0.255 and 1.0.32.7.0.255) seems overwhelming with hundreds of pages of object dictionaries.
    For example, inspecting a raw GET-Request:

    C0 01 C1 00 03 01 00 01 08 00 FF 02 00
    

    How do experienced metering engineers memorize and distinguish these 6 numeric groups in practical development?

    1 Reply Last reply
    0
    • A Offline
      A Offline
      alex_turner
      wrote on last edited by
      #2

      Instead of trying to memorize individual numbers, think of OBIS as a 6-level semantic classification system per Blue Book Section 4.2:

      Group Standard Meaning Intuitive Rule Practical Examples
      A Medium / Abstract What physical commodity? 1 = Electricity, 7 = Gas, 8 = Water, 9 = Heat
      B Channel Which internal path? 0 = No channel / Total, 1..64 = Sub-meter channels
      C Physical Quantity What physical parameter? 1 = Active Energy (+A), 31/32/33 = Voltage (L1/L2/L3), 11/12/13 = Current
      D Measurement Type How is it measured/processed? 8 = Cumulative Energy (integral), 7 = Instantaneous value, 4 = Max demand
      E Tariff / Rate Which pricing tier? 0 = Total (all tariffs), 1 = T1, 2 = T2, 3 = T3
      F Billing Period Which historical snapshot? 255 = Current real-time value, 0 = Previous billing period, 1 = 2 periods ago

      For example:

      • 1.0.1.8.0.255 -> Electricity (1) -> Channel 0 (0) -> Active import (1) -> Cumulative energy (8) -> Total tariff (0) -> Current (255) = Total Active Import Energy (+A).
      • 1.0.32.7.0.255 -> Electricity (1) -> Channel 0 (0) -> Phase B Voltage (32) -> Instantaneous (7) -> Real-time (255) = Phase B Instantaneous Voltage.
      1 Reply Last reply
      0
      • S Offline
        S Offline
        sarah_jenkins
        wrote on last edited by
        #3

        However simple this breakdown looks, it clarifies the entire Blue Book structure.
        Now I can easily recognize why 1.0.2.8.0.255 is active export energy (since C=2 represents active export -A, and D=8 represents cumulative integration).
        Per IEC 62056-61 Clause 4.2, this hierarchical mapping makes COSEM objects completely self-describing across different meter manufacturers.

        1 Reply Last reply
        0

        Hello! It looks like you're interested in this conversation, but you don't have an account yet.

        Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.

        With your input, this post could be even better 💗

        Register Login
        Reply
        • Reply as topic
        Log in to reply
        • Oldest to Newest
        • Newest to Oldest
        • Most Votes


        • Login

        • Don't have an account? Register

        • Login or register to search.
        Powered by NodeBB Contributors
        • First post
          Last post
        0
        • Categories
        • Recent
        • Tags
        • Popular
        • World
        • Users
        • Groups