PLC (G3-PLC / PRIME) Media MAC Framing & Intermittent DLMS Timeouts
-
Field Troubleshooting: DLMS over G3-PLC and PRIME Networks
Power Line Communication (PLC) carries DLMS/COSEM data directly over low-voltage electrical distribution cables. High-frequency noise from inverter air conditioners and solar PV inverters frequently degrades SNR.
Key Diagnosed Issues
- High Packet Fragmentation: G3-PLC 6LoWPAN adaptation layer fragments 1024-byte DLMS PDUs into multiple 128-byte MAC frames. If 1 fragment is lost due to noise, the entire DLMS APDU is dropped.
- Mitigation: Reduce
max_pdu_sizeto 256 or 384 bytes in AARQ. Smaller PDUs fit within 2-3 PLC hops with significantly higher completion probability. - Timeout Tuning: Increase gateway application response timeout (
t_response) from 3.0s to 12.0s when routing through multi-hop mesh repeaters.
-
Adjusting
max_pdu_sizeto 384 bytes on noisy LV feeders increased our daily automated meter reading (AMR) success rate from 81% to 98.6%.
Hello! It looks like you're interested in this conversation, but you don't have an account yet.
Getting fed up of having to scroll through the same posts each visit? When you register for an account, you'll always come back to exactly where you were before, and choose to be notified of new replies (either via email, or push notification). You'll also be able to save bookmarks and upvote posts to show your appreciation to other community members.